The two NOAs do two different jobs
A common misreading: "the products are Miami-Dade approved, so the roof is approved." Not quite. Miami-Dade issues component approvals (what a membrane is) and roof assembly approvals (how a specific stack, fastened a specific way, performs in uplift testing). You need both — and only one of them carries a psf rating.
Polyglass BUR, Modified Bitumen & Synthetic Roofing Membranes and Accessories
- Establishes physical-property testing and traceability of the membranes themselves (ASTM D6163, D6222, D6164…)
- Lists Elastobase V, Elastoflex SA V FR, Polyflex SA P FR by name
- Carries no wind uplift rating — its own limitations say the products are for use within approved roofing system NOA assemblies
- Fire classification is explicitly not part of this acceptance (bring the fire directory listing separately)
Polyglass Self-Adhered Roof System over Wood Decks
- Approves complete tested assemblies: deck + anchor sheet + fasteners + plies + cap, each as a numbered System
- This is where the Maximum Design Pressure (MDP) lives — one rating per system, tied to that system's exact fastening
- Its General Limitation No. 7 requires perimeter/corner fastener enhancement per RAS 117 with PE-sealed calculations
- Sets deck prerequisites (min. 19/32″ plywood, deck fastening pattern)
The assembly, layer by layer
This is Deck Type 1 — the wood-deck configuration used for residential reroofs (shown with System E(8) fastening). Hover or tap any layer to see what it is and where it's approved.
Everything above the deck installs torch-free: the base sheet is nailed, and both membranes above it bond with Polyglass's ADESO self-adhered compound. In uplift, the whole stack is only as strong as the anchor sheet's fasteners — which is why the NOA rating is really a rating of that nailing pattern.
One NOA, many ratings: pick your system, inherit its number
NOA 22-0706.09's cover sheet says "Maximum Design Pressure −112.5 psf." That's the highest rating of any system in the document — not a rating your roof gets automatically. Here's how the wood-deck systems that use this product stack actually break down:
| System | Anchor sheet fastening (field) | Deck prerequisite | MDP (ASD) |
|---|---|---|---|
| E(1) lower-demand sites |
Elastobase V · 11 ga. ring-shank nails + 1-5/8″ tin caps · 8″ o.c. @ 4″ lap + 3 staggered center rows @ 8″ o.c. | Re-nail 8d @ 4″ o.c. or #8 screws @ 6″ o.c. | −52.5 psf |
| E(8) HVHZ workhorse |
12 ga. ring-shank nails + primed tin caps · 6″ o.c. @ lap + 4 staggered rows @ 6″ o.c. | Deck re-screwed #8×3″ @ 6″ o.c. | −97.5 psf with Elastoflex SA V / SA V FR −112.5 psf only with other listed plies (SA V PLUS, XtraFlex) |
And RAS 117 applies no matter which system you pick
Every wood-deck system in this NOA cites General Limitation No. 7: perimeter and corner areas must meet their elevated pressures through increased fastener density calculated per RAS 117, in calculations signed and sealed by a Florida PE. The alternative rule — Limitation No. 9, where one MDP covers all zones — is only in force where the NOA says so, and no system here invokes it. So the sealed RAS 117 sheet isn't an optional workaround; it's the compliance mechanism the approval itself prescribes. A well-chosen system just makes that calculation short.
Here's the reality check the numbers force: at HVHZ design speeds, even a one-story home's field demand runs around −71 psf ASD (170 mph, 10 ft height) — already past E(1)'s −52.5 rating. E(1) has its place at lower design pressures, but for typical Broward/Miami-Dade low-slope reroofs, E(8) is the practical entry point: its −97.5 rating covers the field and perimeter with the standard pattern, and the sealed RAS 117 calculation densifies only the corners.
Where the pressures land: roof zones under ASCE 7-22
Wind suction isn't uniform — corners see roughly twice the field pressure. ASCE 7-22 Figure 30.3-2A divides a low-slope roof into zones using the mean roof height h (not the older "a" strip formula): a perimeter band, L-shaped corner regions extending 0.6h from each corner, and an interior zone. For construction simplicity, practice is to envelope the corners as full 0.6h × 0.6h squares — a 10-ft-tall house gets 6-ft corner squares and a 6-ft edge band.
Try it: HVHZ low-slope uplift estimator
Enter your roof's basics and see the required ASD uplift pressures by zone, how they compare to the NOA system rating, and the RAS 117-style enhanced fastener spacing a sealed calculation would land on. Defaults reflect a typical Broward County one-story home.
How to write the spec (and fill the HVHZ form)
Four moves, in order. This is the same sequence a plan reviewer will check.
- Name the assembly, not just the products. Cite the roof assembly NOA, deck type, and system number — that phrase is what carries the rating. The component NOA and product data sheets ride along as attachments.
- State the required pressures. Site-specific ASCE 7-22 C&C pressures for Zones 1′, 1, 2, and 3 (ASD basis to match the NOA). These go on the HVHZ Uniform Permit Application, Section C.
- Bridge perimeter and corner with RAS 117. Field adequacy is MDP ≥ Zone 1. Zones 2 and 3 get enhanced fastener density from a PE-sealed RAS 117 calculation — spacing per zone goes on the form's anchor-sheet fastening blanks.
- Carry the prerequisites. Deck re-nailing per the NOA deck description, edge metal per RAS 111, fire directory listing attached (the component NOA excludes fire classification), and both NOAs verified current at permit time.