RTU / Rooftop Equipment Wind Force Calculator

ASCE 7-16 / 7-22 rooftop structures and equipment wind forces per Section 29.4.1 (buildings h ≤ 60 ft): lateral force on the projected face, uplift on the plan area, and anchorage / stability screening with a transparent calculation record.

Inputs

All calculations run in your browser. No backend calls are used.

Code Edition and Site Parameters

7-16 places Kd inside qh; 7-22 applies Kd in the force equation. Exposure constants follow the corresponding Table 26.10-1/26.11-1. Net forces are equivalent.

Select V from the wind speed map for your Risk Category.

3-second gust at 33 ft in Exposure C (ASCE 7 Section 26.5).

Height of the supporting roof. Sec. 29.4.1 GCr force form applies to buildings with h ≤ 60 ft.

Used for Ke = e(−0.0000362 × zg) per Table 26.9-1. Ke = 1.0 is always permitted (conservative).

Default 1.00 (flat terrain). See Section 26.8.

0.85 for rooftop equipment per Table 26.6-1.

Equipment Geometry and Coefficients

Sec. 29.4.1 cap: 1.9 (lateral). May be reduced toward 1.0 as Af approaches 0.1 B h.

Sec. 29.4.1 cap: 1.5 (uplift). May be reduced toward 1.0 as Ar approaches 0.1 B L.

Vertical projected area normal to the wind (include curb face exposed to wind).

Use the lowest credible weight (e.g., shipping/empty) when resisting uplift or overturning.

Lateral force is applied at curb height + hu/2.

Used for the rigid-body overturning lever arm b/2.

Curb-to-unit or sled-to-membrane interface. Many AHJs do not permit friction-only restraint.

0.6D + 0.6W governs uplift/overturning resistance under ASD.

Method: Rooftop structures and equipment force form per ASCE 7 Sec. 29.4.1 (buildings h ≤ 60 ft): Fh = qh × (GCr) × Af and Fv = qh × (GCr) × Ar, with Kd placed per the selected edition (inside qh for 7-16; in the force equation for 7-22). Default GCr values are the conservative Sec. 29.4.1 caps (1.9 lateral, 1.5 uplift). Stability screening treats the unit as a rigid body; anchorage design (embedment, hardware, curb/deck capacity) is outside this tool's scope.

Results

No calculation yet

Fill in the form and select Calculate Wind Forces.

Methodology and References

ASCE 7-22 Eq. 26.10-1 velocity pressure (Kd excluded from qh, applied in the force equation) or ASCE 7-16 form (Kd inside qh); rooftop structures and equipment force coefficients per Sec. 29.4.1; Kz evaluated at no less than z = 15 ft (Table 26.10-1, Case 2) using the edition's exposure constants.

Important Disclaimer
  • This calculator is for informational and preliminary screening use only.
  • Use does not create an engineer-client relationship or professional engineering service agreement.
  • Overturning and sliding checks are rigid-body screening values; anchor tension from overturning depends on the actual anchor layout and must be resolved by the engineer of record.
  • Users are responsible for confirming adopted code edition, jurisdictional amendments, and governing load cases.
  • Final design and permit decisions must be reviewed and approved by a licensed professional engineer.
  • WindCalculations.com disclaims liability for losses arising from use or misuse of this tool.